D150-01-00 1 I56-599-03R
B116LP Plug-in Detector Base
For use with the following smoke detectors:
In US: 1151, 2151
In Canada: 1151A, 2151A
In Europe: 1151E, 2151E
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue,
St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which pro-
vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor. (For
installation in Canada, please refer to CAN4-S524, Standard
for the Installation of Fire Alarm Systems and CEC Part 1,
Sec. 32.)
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: The detector used with this base must be
Specifications
Base Diameter: 6.2 inches (157 mm)
Base Height: 0.95 inches (24 mm)
Weight: 0.3 lb. (130 g)
Mounting: 4-inch square box with or without plaster ring. Min. Depth–1.5 inches
4-inch octagon box. Min. Depth–1.5 inches
3-1/2 inch-octagon box. Min. Depth–1.5 inches
50 mm box
60 mm box
70 mm box
Operating Temperature Range: 0° to +49°C (32° to 120°F) US and Canadian Installations
10°to 60°C (14° to 140°F) European Installations
Operating Humidity Range: 10% to 93% Relative Humidity
Electrical Ratings – includes base and detector
System Voltage: 24 VDC
Maximum Ripple Voltage: 4 Volts peak to peak
Start-up Capacitance: 0.02µF Maximum
Standby Ratings: 15 VDC Minimum
35 VDC Maximum
120 µA Maximum
Alarm Ratings: 8 V Minimum at 16 mA
12 V Maximum at 100 mA
(Alarm current MUST be limited to 100 mA maximum by the control panel.)
Relay Contact Ratings:
Resistive or Inductive (60% power factor) Load
Form C:* 2.0A @ 30 VAC/DC
0.6A @ 110 VDC
1.0A @ 125 VAC
Reset Voltage: 1.4 VDC Minimum
Reset Time: 0.3 Seconds Maximum
Start-up Time: 34.0 Seconds Maximum
*For Canadian installations relay contact ratings are 2.0A @ 30 VAC/DC.
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.
General Description
The model B116LP plug-in detector base is used with
System Sensor model 1151, 1151A, and 1151E ionization
detector heads and model 2151, 2151A, and 2151E photo-
electronic detector heads. The capability of plugging these
detectors into a variety of special bases makes them more
versatile than equivalent direct-wired models. Refer to the
System Sensor catalog for other available plug-in detector
bases.
Przeglądanie stron 0
1 2 3 4

Podsumowanie treści

Strona 1 - B116LP Plug-in Detector Base

D150-01-00 1 I56-599-03RB116LP Plug-in Detector BaseFor use with the following smoke detectors:In US: 1151, 2151In Canada: 1151A, 2151AIn Europe: 1151

Strona 2 - D150-01-00 2 I56-599-03R

D150-01-00 2 I56-599-03RThe B116LP base is intended for use in 2-wire systems,with screw terminals provided for power and relay contactconnections. Th

Strona 3 - D150-01-00 3 I56-599-03R

CAUTIONOnce all the detector bases have been wired and mounted,and the loop wiring has been checked, the detector headsmay be installed in the bases.

Strona 4

D150-01-00 4 I56-599-03R© 2001 System SensorThree-Year Limited WarrantySystem Sensor warrants its enclosed smoke detector base to be free fromdefects